Sunday, January 23, 2011

O.C and S.C Tests on Transformers


1. Open-circuit or No-load Test. This test is performed to determine core or iron loss, Piand no-load current I0. This test is helpful in determination of magnetizing component Im’energy component Ie and so no-load resistance R0 being given as V1/Ie and no-load reactance given as V1/Im.
In this test secondary (usually high voltage) winding is left open, all metering instruments (ammeter, voltmeter and wattmeter) are connected on primary side and normal rated voltage is applied to the primary (low voltage) winding, as illustrated below   


Open-circuit or No-load Test.JPG
(source:Google Images)
Iron loss P1 = Input power on no-load – W0 watts (wattmeter reading)
No-load current = 0 amperes (ammeter reading)
Angle of lag, Ø0 = cos-1 Wo/V1Io
e = I0 cos Ø0 and     Im = √I2o - I2e
Caution: Since no load current I0 is very small, therefore, pressure coils of watt meter and the volt meter should be connected such that the current taken by them should not flow through the current taken by them should not flow through the current coil of the watt meter.
2. Short-circuit or Impedance Test. This test is performed to determine the full-load copper loss and equivalent resistance and reactance referred to secondary side. 
In this test, the terminals of the secondary (usually the low voltage) winding are short – circuited, all meters (ammeter, voltmeter and wattmeter) are connected on primary side and a low voltage, usually 5 to 10 % of normal rated primary voltage at normal frequency is applied to the primary, as shown in fig below. The applied voltage to the primary, say Vs’ is gradually increased till the ammeter A indicates the full load current of the side in which it is connected. The reading Ws of the wattmeter gives total copper loss (iron losses being negligible due to very low applied voltage resulting in very small flux linking with the core) at full load. Le the ammeter reading be Is.
Short-circuit or Impedance Test.JPG
(Source: Google Images)
          
Full load copper loss, Pc= I2s R1 = Ws
Equivalent resistance referred to primary, R'1  = Ws/I2s
Equivalent impedance referred to primary,  = Z'1  = Vs/Is                  
Equivalent impedence referred to primary, X'1 = √(Z'1)2  - (R'1)2'
3. Sumpner’s Test or Back to Back Test. This test is mainly performed to determine temperature rise. In this test two transformers are loaded fully, in similar way as two dc machines in a regenerative test, and the power required from the supply is just to meet the iron and full load copper losses of the two transformers.

0 comments:

Post a Comment

Get free traffic to your Blog